Ask an Expert
Discuss My Needs
Menu
Discuss My Needs
Ask an Expert
Keyes Life Safety

Our Life Safety educational resource hub is full of healthcare knowledge to help you be better informed of the changing world around you. 

Rather than sit back and act on decisions made by others, we are leading the charge as it relates to identifying best practices for Life Safety Code® and compliance. We have real people that give our clients real information that can be put into practice.

Interested in reading our experts' take on Life Safety? Then subscribe to our free blog below! We discuss readers' questions, share interesting observations from the field, and more.

Air Handler Unit

by Brad Keyes, CHSP, on Jul 15, 2019 1:00:37 AM

Q: Can we have a fan unit installed in a clean supply room? We have a room where an air handler unit is installed for cooling another equipment room. The unit is in the open and clean supplies are near it. Is this a violation of a code or standard?

A: Sounds like the room is now a mechanical room with clean supplies in it. As far as the Life Safety Code goes, and any referenced NFPA standards, I don’t see a problem. You must maintain 36-inches clearance around the equipment and have clear access to the unit. All electrical connections need to be enclosed (inside junction boxes, etc.).

If the clean supplies are combustible, then the room must be constructed to be a hazardous room. Check with your state and local AHJ to determine if they have any other requirements.

Topics:Air HandlersClean Supply Room

Real people. Real solutions.

We help you be better informed of the changing world around you.  Our life safety blog answers your real world questions! 

More...

More...

Subscribe to Updates

We care and want to help.

We want to help coach, guide, and navigate you through all things Life Safety.
DISCUSS MY NEEDS