Hand Washing Sinks

by Brad Keyes, CHSP, on Jul 12, 2019 1:00:36 AM

Q: We have a relatively new Infection Control team.  They are performing rounds and having mock surveys with a nurse-consultant that cites issues from the 2014 FGI in areas that are much older.  The issue comes in when we are required to install new sinks (dirty, clean and a hand washing) in existing spaces.  We are a mixed hospital, some new that has to meet 2014 FGI due to new renovations.  What are your thoughts on the older areas that have not been renovated?  I am working with a design professional to see how he would design a space for the number of sinks and what reference he should use.  If it is simple and best practice to install them, I am all for it but some of the renovations come with a significant space or capital impact.  I am not sure if this is something you can help guide with or not.

A: According to Joint Commission’s standard EC.02.06.05, EP 1, the FGI Guidelines (2014 edition) is only used when planning for new, altered, or renovated spaces. Tell the nurse-consultant surveyor she is mistaken. She cannot apply a new guideline to an existing condition.

Now… if there was a requirement to have hand-washing sinks in the room at the time the room was designed or renovated, then she is correct and the sinks need to be installed. But if she plays that card, then she needs to provide evidence that there was a regulation (state, local, or otherwise) that required the sink at the time the room was designed and constructed.

Topics:Joint CommissionFGI GuidelinesHand Washing Sink

Real people. Real solutions.

We help you be better informed of the changing world around you.  Our life safety blog answers your real world questions! 