      Sterile Processing Room

      by Brad Keyes, CHSP, on Jun 8, 2020 12:00:00 AM

      Q: Would a sterile processing room be considered a hazardous area? There are not a lot of combustible supplies and the only flammable liquid is ethyl alcohol. There is glutaraldehyde which presents a health hazard. I’m not sure what type of protection the room would require.

      A: Typically, hazardous areas in healthcare are identified by the number of combustible items stored in a given room or area. But according to section 3.3.21.4 of the 2012 LSC, a hazardous area is any area that poses a degree of hazard greater than that normal to the general occupancy of the building. So, technically, a room where glutaraldehyde (or other hazardous chemicals) is used could be considered a hazardous room. But that’s going to be a judgment call and not all surveyors will think alike on this subject.

      My advice is to be very conservative and consider the room to be a hazardous room as long as you’re using hazardous chemicals. This would likely require the room to be built to 1-hour fire-rated construction, with ¾ hour fire rated doors that self-close and positively latch, and the room will need to be sprinklered.

       

      Topics: Hazardous Areas

      We care and want to help.