Ask an Expert
Discuss My Needs
Menu
Discuss My Needs
Ask an Expert
Keyes Life Safety

Our Life Safety educational resource hub is full of healthcare knowledge to help you be better informed of the changing world around you. 

Rather than sit back and act on decisions made by others, we are leading the charge as it relates to identifying best practices for Life Safety Code® and compliance. We have real people that give our clients real information that can be put into practice.

Interested in reading our experts' take on Life Safety? Then subscribe to our free blog below! We discuss readers' questions, share interesting observations from the field, and more.

Q&AHeadroom

Q: Is there a minimum height requirement for a fully sprinklered corridor? A: Yes… you will find the minimum headroom height requirement in section 7.1.5.1 of the 2012 LSC. Means …

Brad Keyes, CHSP | Sep 21, 2017
ArticleHeadroom

Another area of the Life Safety Code that is not well known by many is the requirement for headroom, which is defined as the distance between the floor and the …

Brad Keyes, CHSP | Aug 29, 2013

Real people. Real solutions.

We help you be better informed of the changing world around you.  Our life safety blog answers your real world questions! 

More...

More...

Subscribe to Updates

We care and want to help.

We want to help coach, guide, and navigate you through all things Life Safety.
DISCUSS MY NEEDS